Product DescriptionTypical ApplicationsTypical PropertiesOrderingProduct Photos



E/Paintable Insulation™ is a unique formula of silicone rubber technology offering high dielectrict strength in a paintable insulation.
  • Prevents power system outages and damage caused by animals
  • Has high dielectric strength
  • Has excellent atmospheric and chemical resistance
  • Becomes a tough, tear-resistant coating
A one-coat application of 30 mils on metal surfaces provides 10kV insulation strength. When applied to both ends of electrical insulators, metal support structures, bushings and pothead there is sufficient insulation obtained to guard against animal caused flashovers. When applied to the surface of electrical insulation such as FRP Barrier Boards, E/Paintable Insulation™ imparts water repellency and arc-track resistance.

E/Paintable Insulation™
features superb unprimed adhesion to galvanized metal and most insulating ceramic, glass and plastic materials.


E/Paintable Insulation™ is used by:
  • Power & Electrical Utilities
  • Electrical Contractors
  • Telecommunication Contractors
  • Cable Contractors
  • Independent Power Producers
For the purpose of:
  • Preventing cracks and any further damage on costly and difficult to replace apparatus, post and bushings
  • Prevents electrical tracking
  • Prevents ultraviolet degradation and stress corrosion failures in outdoor environments
  • Preventing moisture ingress
  • Ideal for street lighting and buried applications
  • Waterproofs and seals

UNCURED      
Type..............One part, RTV
Appearance..................Thick Paint
Specific Gravity...........................1.25
Application Temp Range, oF (oC)...............0oF to 120oF
(-18oC to 50oC)
Cure Method...Oxime, moisture cure
Skin-over time at std conditions*, min.....................60
Cure time at std conditions*, hour...........................24
Flash Point, oF (oC)......................109oF
(43oC)
CURED at standard conditions* for 7 days
Durometer Hardness (ASTM D2240, ShoreA), points.....50
Tensile Strength (ASTM D412), psi (kg/cm2).........480 (33.75)
Elongation at break (ASTM D412), %..................200
Tear Resistance (ASTM D624, Die B), ppi (kN/m)...37 (6.5)
Shrink Factor..............Nil
Dielectric Strength (ASTM D149), V/mil (kV/cm)..385 (152)
Volume Resistivity (ASTM D257), ohm•cm...........3.0 x 1015
Dissipation Factor (ASTM D150) 100Hz to 100Hz........0.01
Dielectric Constant (ASTM D150) 100Hz to 100Hz.........4.0
Thermal Conductivity, W/m•k.........................0.5




QUANTITY - E/PI - G

MIDSUN GROUP stocks a limited supply of E/Paintable Insulation™. Most orders are made to order, therefore a four to six week lead time AT MINIMUM is needed to fulfill orders. Rush Delivery is available at a surcharge.


E/Paintable Insulation™
IS NOT A RETURNABLE ITEM


Call (860) 378-0100 Today to
Request Pricing and Place Your Order!




E/Paintable Insulation :: 1 E/Paintable Insulation :: 2